Tripp Lite series SmartOnline 5000VA 4500W 208V Online Double-Conversion UPS - L6-30P, 2 L6-20R, 2 L6-30R, Hardwired Output, Network Card, Extended Run, 3U Rack/Tower
Product Name |
Eaton Tripp Lite series SmartOnline UPS
|
Catalog Number |
SU5000RT
|
UPC |
786689811723
|
Product Length/Depth |
25.04 in
|
Product Height |
5.12 in
|
Product Width |
17.32 in
|
Product Weight |
114.02 lb
|
Compliances |
FCC Compliant
CE Marked RoHS FCC Class A ENERGY STAR certified REACH |
Certifications |
NOM
IEC/EN 62040-2 CSA 22.2 UL 1778 cTUVus |
Topology |
Online/Double-conversion
|
Form factor |
Rack/tower
|
Rack size |
3U
|
Color |
Black
|
VA rating |
5000 VA
|
Wattage |
4500 W
|
Rack mounting kit |
Yes
|
Package contents |
|
Surge protection |
Yes
|
Internal bypass |
Yes
|
Current Crest Ratio |
3:1
|
Input connection |
Hardwire; L6-30P
|
Input cord length |
10 ft
|
Input nominal voltage |
200 VAC/208 VAC/220 VAC/230 VAC/240 VAC
|
Nominal frequency |
50/60 Hz
|
Input frequency range |
50/60 Hz
|
Input power factor |
>0.99 typical
|
Receptacle |
(2) L6-20R; (2) L6-30R; Hardwire
|
Number of Outputs L6-20R |
2
|
Number of Outputs L6-30R |
2
|
Number of outputs hardwired |
1
|
Output waveform |
True sine wave
|
Voltage |
208 V
|
Output nominal voltage |
208V default (200/208/220/230/240V)
|
Runtime graph |
|
Battery replacement |
EBP-1803
|
Battery type |
Valve Regulated Lead Acid (VRLA)
|
Extended battery capability |
Add up to 4 extended battery modules (EBM). Part number BP180RT
|
Standard factory warranty |
|
Extended service plans |
|
Runtime at half load |
11 min
|
Ethernet interface |
Yes
|
Includes network card |
Yes
|
Software compatibility |
PowerAlert
|
Altitude |
<1000m for nominal power, 10% power degrading every 1000m (up to 3000m)
|
Noise level |
<45 dB at 1 meter
|
Relative humidity |
0-95% non-condensing
|
Front Panel LCD Display |
LCD graphical display
|
Input Plug Type |
NEMA L6-30P
|
Output Receptacles |
L6-30R
L6-20R Hardwire |
Product Features |
Emergency Power Off (EPO)/Remote On-Off (ROO)
Expandable Runtime L6-30P 10ft. |
Product Highlights |
Protects equipment against blackouts, brownouts, transient surges and line noise
Keeps equipment running during outages to allow time for file saves and safe shutdown Pre-installed WEBCARDLXE network card enables full remote access and control Menu-driven LCD interface keeps you updated on critical load information in real time Optional extended battery modules allow extended runtime to keep equipment powered |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at https://tripplite.eaton.com/products/power-alert
|
Network Management Cards |
WEBCARDLXE
|
Network Management Cards Details |
Network management card included
|
Efficiency at max. load |
93%
|
Input voltage range |
200-240V
|
Max number of battery packs |
4
|
Output frequency |
50/60 Hz
|
Output power factor |
0.9
|
Phase (input) |
Single-phase
|
Runtime at full load |
3 min. (4500W)
|
Communication interface |
USB and DB9 serial cables included
USB Contact closure RS-232 Included network card |
Battery Access |
Battery access door
|
Typical Battery Runtime |
Expandable Runtime
|
Dc Voltage |
180
|
Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
Communications Cable |
USB and DB9 serial cables included
|
Input Circuit Breakers |
Recommended 30A upstream
|
Optional Mounting Accessory Notes |
2 post rail kit available, part # RK2PC
|
Output Circuit Breakers |
20A breaker protects L6-20R outlets
|
High Voltage Transfer to Battery Power |
276V
|
Low Voltage Transfer to Battery Power |
176V
|
Application |
Mission Critical Applications
|
Switch configuration |
RPO / ROO
|
AC suppression joule rating |
390
|
Housing material |
Metal
|
Output AC waveform (AC mode) |
Pure Sine wave
|
Output AC waveform (battery mode) |
Pure sine wave
|
Output Capacity (kVA) |
5
|
Output Capacity (kW) |
4.5
|
Output Capacity (VA) |
5000
|
Output Capacity (Watts) |
4500
|
Operating Elevation |
<1,000 meters for nominal power; 10% power derating every 1000 meters (up to 3000 meters) at 40°C
|
AC Suppression Response Time |
0 ms
|
Alarm Interface |
Press ESC to silence the alarm
|
Audible Alarms |
Audible alarm indicates utility failure, low-battery, overload, other UPS/Battery fault or remote shutdown conditions
|
Battery Start Capability |
Cold-start operation supported
|
Cooling Method |
Fan
|
Battery Replacement Description |
Hot-swappable, user replaceable batteries. UPS requires 1 Replacement Battery Cartridge.
|
LED Indicators |
4 status-indicating LEDs
|
Frequency Rating Details |
50 or 60Hz, autosensing or configurable as a frequency converter
|
Minimum Required Rack Depth With External Battery Pack |
31
|
Output Voltage Regulation (Line Mode) |
+/- 1%
|
Output Voltage Regulation(Battery Mode) |
+/- 1%
|
Recommended Electrical Service |
30A
|
Storage Temperature |
With battery: 32° to 104°F (0° to 40°C); without battery: -13° to 131°F (-25° to 55°C)
|
Included Mounting Accessory Description |
Includes 4 post rackmount and tower pedestal accessories
|
Input Nominal Voltage Description |
Factory configured to 208V
|
Network Monitoring Port Description |
WEBCARDLXE Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications; not compatible with WEBCARDLX
|
Nominal Voltage Details |
200V, 208V, 220V, 230V, 240V
|
Voltage Regulation Description |
Online, double-conversion power conditioning
|
Plug Type |
NEMA L6-30P
|
Maximum Input Amps |
23
|
Minimum Required Rack Depth (cm) |
78.74
|
Minimum Required Rack Depth (inches) |
31
|
Total Harmonic Distortion |
< 2% THDV on linear load; < 5% THDV on non-linear load
|
UPS Input Cord Length (m) |
3.1
|
Power Mode Transfer Time |
0 ms
|
Optional Accessories |
2 post rackmount (RK2PC)
|
EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
UPS Input Connection Type |
Hardwire
L6-30P |
External Battery Pack Compatibility |
BP180RT
|
Green Energy-Saving Features |
High efficiency economy mode operation
|
High Availability UPS Features |
Automatic voltage regulation (AVR)
Hot swappable batteries On-Line/Double-Conversion Remote management Expandable battery backup Pure sine wave output Zero transfer time Surge/noise protection |