Eaton Moeller series NZM - Molded Case Circuit Breaker. Box terminal, 3p, up to 630 A

Spécifications générales

Product Name
Eaton Moeller series NZM connection type
Catalog Number
260042
Model Code
NZM3-XKC
EAN
4015082600426
Product Length/Depth
120.5 mm
Product Height
275 mm
Product Width
140 mm
Product Weight
0.41 kg
Compliances
IEC
UL/CSA
RoHS conform
Certifications
CSA (File No. 22086)
UL (Category Control Number DIHS)
CSA (Class No. 1432-01)
UL489
CSA-C22.2 No. 5-09
CSA certified
IEC60947
UL listed
UL (File No. E31593)
CE marking

Additional information

Model
Other

Delivery program

Amperage Rating
≦ 630 A
Frame
NZM3
Number of poles
Three-pole
Suitable for
Copper cable
Three-pole
Type
  • Accessory
  • Box terminal
Used with
NZM3(-4), PN3(-4), N(S)3(-4)

Design verification as per IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Technical Data - Electrical

Amperage Rating
≦ 630 A

Technical Data - Mechanical - Terminals

Terminal capacity (copper strip)
Max. 500 A: 6 segments of 16 mm x 0.8 mm - 10 segments of 24 mm x 1 mm or 11 segments of 21 mm x 1 mm
630 A: 10 segments of 24 mm x 1 mm + 5 segments of 24 mm x 1 mm or 8 segments of 24 mm x 1 mm (2x)
Terminal capacity (stranded cable)
35 mm² - 240 mm² (1x)
2 - 500 AWG/kcmil (1x)
25 mm² - 120 mm² (2x)
4 - 250 AWG/kcmil (2x)

Exporter les spécifications du produit

Remarque : L’absence d’un ou plusieurs fichiers dans un ficher .zip téléchargé peut être causée par l’absence de prise en charge du type de fichier pour un téléchargement groupé.

Vous avez besoin d’un support produit?

Assistance de la part d’Eaton

Des questions sur ce produit ?

0 800 336 858